Description
Specifications
Model
D30 (RWC030) / D50 (RWC050)
Input Power
1-phase, 200-240 V, 50/60 Hz
Total Capacity *
D30: 30 kW
D50: 50 kW
Sensible Heat Factor (SHF): 1
Rating Input Power
D30: 0.56 kW
D50: 0.66 kW
Fan Type: EC
Fan Quantity: 4
Air Flow
D30: 3605 CFM
D50: 3885 CFM
Water Flow
D30: 55 LPM
D50: 90 LPM
Valve: Two way valve (FC type)
Piping Connection: Top / Bottom
Pipe Size
D30: 1?
D50: 1 1/4?
Water Leakage Detector: Standard, 4m length
User Interface: LCD screen with 4 LED indicators
Complies With: UL 60335 , CE
Dimensions (W ? H ? D): 600 x 1970 x 345 mm (23.6 x 77.5 x 13.5 in)
Weight
D30: 90 kg (198.4 Ib)
D50: 98 kg (216 Ib)
* Conditions for rated capacity for D30 at return air 42?C (108?F), inlet water 12?C (54?F) and outlet water 20?C (68?F)
* Conditions for rated capacity for D50 at return air 50?C (122?F), inlet water 12?C (54?F) and outlet water 20?C (68?F)
All specifications are subject to change without prior notice.
Optional Items
Air Pressure Control
PICV Valve
BACnet
SNMP
Inlet Water Solenoid Valve
T/RH Sensor at Cold Aisle
Flow Meter
Quick Disconnect Couplings
Dual Power Feed/ ATS