Description
Specifications
Model: R30 / R45
Input Power: 3-phase + N, 380-415 V, 50/60 Hz
Total Capacity *
R30: 30 kW
R45: 45.6 kW
Sensible Capacity *
R30: 30 kW
R45: 45.5 kW
Rating Input Power
R30: 10.3 kW
R45: 15 kW
Fan Type: EC
Reheater (optional)
Type: PTC
Capacity
R30: 3 kW
R45: 6 kW
Humidifier (optional)
Type: Wet membrane or electrode
Capacity: 3 kg/hr
Connection: Top / Bottom
Communication: RS-485 x 1, FE port, USB port, Dry contact
User Interface: 10? Touch panel
Safety Certification: CE, RCM
Dimensions (W ? H ? D)
R30: 300 x 2000 x 1090 mm
R45: 600 x 2000 x 1090 mm
Weight
R30:
Cooling: 216 kg
Cooling with reheater & wet membrane humidifier: 220 kg
Cooling with reheater & electrode humidifier: 223 kg
R45:
Cooling: 300 kg
Cooling with reheater & wet membrane humidifier: 303 kg
Cooling with reheater & electrode humidifier: 306 kg
* Capacity is measured at 40.6?C return air dry bulb, 21.6?C wet bulb and 35?C outdoor temperature.
Outdoor Condenser
Model
R30 Condenser: RDA037
R45 Condenser: RDA059
Input Power: 3-phase, 380-415 V, 50/60 Hz
Fan
Type: Variable fan speed
Number: 1
Dimensions (W ? H ? D) – Up Flow: 1725 x 1120 x 1100 mm
Weight
R30 Condenser: 110 kg
R45 Condenser: 120 kg
All specifications are subject to change without prior notice